Wednesday, 12 August 2015

Fujitsu Air Conditioning Complete List Of Fault Codes For Wall Mounted Multi Room Models




Fujitsu Air Conditioning Complete List Of Fault Codes 



For Wall Mounted Multi Room Models



Initial Display                                                                                                   Further Interrogation by Pressing Test Button on Infra Red RC


Red
Green
Meaning
Red
Green
Meaning
2 Flashes
Blinks
ID Sensor Failure
Blinks
2 Flashes
ID Air Sensor
2 Flashes
Blinks
ID Sensor Failure
Blinks
3 Flashes
ID Pipe Sensor
4 Flashes
Blinks
ID Control Error
Blinks
2 Flashes
Manual Auto Button Error
4 Flashes
Blinks
ID Control Error
Blinks
4 Flashes
Power Source Failure
5 Flashes
Blinks
Communication Failure
Blinks
2 Flashes
Reverse Communication Failure
5 Flashes
Blinks
Communication Failure
Blinks
3 Flashes
Forward Communication Failure
6 Flashes
Blinks
ID Fan Failure
Blinks
2 Flashes
Motor locked
6 Flashes
Blinks
ID Fan Failure
Blinks
3 Flashes
Motor RPM Incorrect
Blinks
2 Flashes
OD Thermistor Fail
2 Flashes
Blinks
OD Discharge Sensor Fail
Blinks
2 Flashes
OD Thermistor Fail
4 Flashes
Blinks
OD Pipe Sensor Fail
Blinks
2 Flashes
OD Thermistor Fail
6 Flashes
Blinks
OD Air Sensor Fail
Blinks
2 Flashes
OD Thermistor Fail
8 Flashes
Blinks
Compressor Temp Sensor Fail
Blinks
2 Flashes
OD Thermistor Fail
9 Flashes
Blinks
2 Way Valve Sensor Fail
Blinks
2 Flashes
OD Thermistor Fail
10 Flashes
Blinks
3 Way Valve Sensor Fail
Blinks
3 Flashes
Pressure Switch
2 Flashes
Blinks
Pressure Switch
Blinks
4 Flashes
ID Units Incorrect
2 Flashes
Blinks
Incorrect Indoor Unit Index
Blinks
5 Flashes
Inverter Failure
2 Flashes
Blinks
IPM Failure
Blinks
5 Flashes
Inverter Failure
5 Flashes
Blinks
Compressor Failure




Contact Us With Your Spares Inquiry Below:


Call: +44(0)845 567 7080

E-mail: Info@orionair.co.uk 

Fujistu Air Conditioning Fault Codes For wireless indoor units AUY, ABY and AWY Models. Including Multi Systems (Not J Series or VRF)

Fujistu Air Conditioning Fault Codes For wireless indoor units AUY, ABY and AWY Models. Including Multi Systems (Not Series or VRF)





Red Light Operation
Green Light Timer
Yellow Light Swing

On


Normal
On
Slow Blink
Slow Blink
Test
Blinks
Blinks
Off
ID PCB Fail
Blinks
Blinks
Blinks
OD PCB Fail
Blinks
2 Pulses
Off
OD Power Connection Failure
Blinks
3 Pulses
Off
OD Unit Pipe Sensor Fail
Blinks
4 Pulses
Off
OD Unit Air Sensor Fail
Blinks
4 Pulses
Blinks
OD Unit Air Sensor Short
Blinks
5 Pulses
Off
OD Unit Discharge Sensor Fail
Blinks
5 Pulses
Blinks
OD Unit Discharge Sensor Short
Blinks
6 Pulses
Off
High Pressure
Blinks
7 Pulses
Off
High Discharge or Compressor Temp
Blinks
9 Pulses
Off
OD Unit Compressor Temp Sensor
Blinks
10 Pulses
Off
IPM Error
Blinks
11 Pulses
Off
CT Error
Blinks
12 Pulses
Off
AFM Filter Error
Blinks
13 Pulses
Off
Compressor Error
Blinks
14 Pulses
Off
OD Fan Motor Fail
2 Pulses
Blinks
Off
Air Sensor Open
2 Pulses
Blinks
Blinks
Air Sensor Closed
3 Pulses
Blinks
Off
Pipe Sensor Open
3 Pulses
Blinks
Blinks
Pipe Sensor Closed
4 Pulses
Blinks
Off
Drain Problem
5 Pulses
Blinks
Off
Communication Error
5 Pulses
Blinks
Blinks
OD PCB or Wiring Error
6 Pulses
Blinks
Off
Indoor Fan Failure
          




Contact Us With Your Spares Inquiry Below:


Call: +44(0)845 567 7080

E-mail: Info@orionair.co.uk