A++/A+++ Rated energy product
The R32 MXS-F outdoor multi-split system allows up to four M Series or Mr Slim wall mounted, cassette, ducted or ceiling suspended indoor units of different capacities to be operated from a single outdoor unit. This makes it an economic and efficient answer for multi-room applications, whilst also offering space saving benefits. Up to four indoor units may be connected to a single outdoor unit Energy saving inverter controlled outdoor unit adjusts compressor performance to economically match the demand for heating and cooling Units may be added within the capacity of the system as requirements change Capacities of indoor units may be mixed to suit individual rooms.
The R32 MXS-F outdoor multi-split system allows up to four M Series or Mr Slim wall mounted, cassette, ducted or ceiling suspended indoor units of different capacities to be operated from a single outdoor unit. This makes it an economic and efficient answer for multi-room applications, whilst also offering space saving benefits. Up to four indoor units may be connected to a single outdoor unit Energy saving inverter controlled outdoor unit adjusts compressor performance to economically match the demand for heating and cooling Units may be added within the capacity of the system as requirements change Capacities of indoor units may be mixed to suit individual rooms.
Key product Feature's:
- Multiple indoor units connected to a single outdoor unit
- Single outdoor unit for minimal noise and space impact
- Energy saving inverter controlled performance A+++
- Compact design R32 outdoor unit
- Mixture of different types of indoor unit
- High SCOP
- Auto re-start after power interruption
- PRE-CHARGED WITH R32 REFRIGERANT
- Fault diagnosis
MXZ-F R32 Outdoor Units:
MXZ-F - OUTDOOR UNITS
|
MXZ-2F33VF
|
MXZ-2F42VF
|
MXZ-3F54VF
|
MXZ-3F68VF
|
MXZ-4F72VF
|
NUMBER OF CONNECTABLE INDOOR UNITS
|
2
|
2
|
2 - 3
|
2 - 3
|
2 - 4
|
CAPACITy (kW) Heating (nominal)
|
4.0 (1.0-4.1)
|
4.5 (1.0-4.8)
|
7.0 (2.6-9.0)
|
8.6 (2.6-10.6)
|
8.6 (3.4-10.7)
|
Cooling (nominal)
|
3.3 (1.1-3.8)
|
4.2 (1.1-4.4)
|
5.4 (2.9-6.8)
|
6.8 (2.9-8.4)
|
7.2 (3.7-8.8)
|
Heating (UK)
|
3.32 (0.83-3.40)
|
3.74 (0.84-3.99)
|
5.81 (2.16-7.47)
|
7.14 (2.16-8.80)
|
7.14 (2.82-8.89)
|
Cooling (UK)
|
3.23 (1.07-3.72)
|
4.12 (1.08-4.32)
|
5.3 (2.85-6.67)
|
6.66 (2.84-8.23)
|
7.0 (3.59-8.56)
|
COP / EER (nominal)*1
|
4.40 / 3.90
|
5.10 / 4.30
|
4.60 / 4.10
|
4.50 / 3.70
|
4.60 / 3.90
|
SCOP / SEER (BSEN14825)
|
4.16 / 6.13
|
4.60 / 8.69
|
4.61 / 8.52
|
4.12 / 7.96
|
4.07 / 8.13
|
ErP ENERGy EFFICIENCy CLASS Heating/Cooling
|
A+ / A++
|
A++ / A+++
|
A++ / A+++
|
A+ / A++
|
A+ / A++
|
MAX AIRFLOW (m3/min) Heating/Cooling
|
33.7 / 32.9
|
33.3 / 27.7
|
43.0 / 42.1
|
43.0 / 42.1
|
43.0 / 42.1
|
SOUND PRESSURE LEVEL (dBA) Heating/Cooling
|
50 / 49
|
50 / 44
|
50 / 46
|
53 / 48
|
54 / 48
|
SOUND POWER LEVEL (dBA) Cooling
|
60
|
59
|
59
|
63
|
63
|
DIMENSIONS (mm) Width x Depth x Height
|
800 x 285 x 550
|
800 x 285 x 550
|
840 x 330 x 710
|
840 x 330 x 710
|
840 x 330 x 710
|
WEIGHT (kg)
|
33
|
37
|
58
|
58
|
59
|
ELECTRICAL SUPPLy
|
220-240v, 50Hz
|
220-240v, 50Hz
|
220-240v, 50Hz
|
220-240v, 50Hz
|
220-240v, 50Hz
|
PHASE
|
Single
|
Single
|
Single
|
Single
|
Single
|
POWER INPUT (kW) Heating/Cooling (nominal)
|
0.909 / 0.846
|
0.88 / 0.98
|
1.52 / 1.32
|
1.91 / 1.84
|
1.87 / 1.85
|
Heating/Cooling (UK)
|
0.82 / 0.68
|
0.90 / 0.78
|
1.38 / 1.06
|
1.73 / 1.47
|
1.69 / 1.48
|
STARTING CURRENT (A)
|
4.6
|
4.2
|
7.0
|
10.5
|
10.0
|
RUNNING CURRENT (A) Heating/Cooling [MAX]
|
4.6 / 4.3 [10.0]
|
4.2 / 4.5 [12.2]
|
7.0 / 5.9 [18.0]
|
10.5 / 9.6 [18.0]
|
10.0 / 9.5 [18.0]
|
INTERCONNECTING CABLE No. CORES
|
4 Core
|
4 Core
|
4 Core
|
4 Core
|
4 Core
|
TOTAL PIPE LENGTH (m)
|
20
|
30
|
50
|
60
|
60
|
MAX PIPE LENGTH PER INDOOR UNIT (m)
|
15
|
20
|
25
|
25
|
25
|
MAX HEIGHT DIFFERENCE (m)
|
10
|
15 (10 if OU higher than IU)
|
15 (10 if OU higher than IU)
|
15 (10 if OU higher than IU)
|
15 (10 if OU higher than IU)
|
CHARGE REFRIGERANT (kg) /
CO2 EQUIVALENT (t) - R32 (GWP 675)
|
1.00 / 0.68 (20m)
|
1.20 / 0.81 (20m)
|
1.40 / 0.95 (50m)
|
1.40 / 0.95 (60m)
|
1.40 / 0.95 (60m)
|
MAX ADDITIONAL REFRIGERANT (kg) /
CO2 EQUIVALENT (t) - R32 (GWP 675)
|
1.00 / 0.68
|
1.40 / 0.95
|
2.40 / 1.62
|
2.40 / 1.62
|
2.40 / 1.62
|
FUSE RATING (BS88) - HRC (A)
|
16
|
16
|
25
|
25
|
25
|
No comments:
Post a Comment