Full List Of Samsung Air Conditioning Error Codes
Code
|
Explanation & Check Points
|
|
|
|
|
||||||||
|
|
|
|
|
|
||||||||
Ch
|
Compressor Starting Delay - Crankcase
heater initiated
|
|
|
||||||||||
"P0"
|
System down due to high temperature discharge
sensor
|
|
|||||||||||
"P1"
|
System down due to the high
temperature of condenser
|
|
|
||||||||||
"P2"
|
Sump Comp Down
|
|
|||||||||||
"P3"
|
System down due to the lower
temperature switch detection
|
|
|
||||||||||
"P4"
|
System Start down due to reverse phase
of the 3 phase
|
|
|||||||||||
"P5"
|
System down due to frozen heat
exchanger
|
|
|
|
|||||||||
"P6"
|
Error of momentary power failure
(dissapears when unit is off/on)
|
|
|||||||||||
"P7"
|
Compressor down due to protection
control of high pressure sensor
|
|
|||||||||||
"P8"
|
Compressor down due to protection
control of low pressure sensor
|
|
|||||||||||
"P9"
|
Problem removing frost
|
|
|
|
|
||||||||
"PA"
|
Compressor down due to protection
control of condensation ratio
|
|
|||||||||||
|
|
||||||||||||
"t1"
|
Error of OUT TEMP sensor (OPEN/SHORT)
|
|
|
|
|||||||||
"t2"
|
Error of COND TEMP sensor
(Open/short)
|
|
|||||||||||
"t3"
|
Error of PWM Discharge TEMP sensor
(Open/Short)
|
|
|
|
|||||||||
"t4"
|
Error of liquid refrigerant pipe
(cond out) Temp (Open/short)
|
|
|||||||||||
"t5"
|
Error of OIL TEMP sensor (Open/Short)
|
|
|
|
|||||||||
"t6"
|
Error of Suction temp sensor
(Open/Short)
|
|
|||||||||||
"t7"
|
Error of high pressure sensor
(Open/Short)
|
|
|
|
|||||||||
"t8"
|
Error of low pressure sensor
(Open/Short)
|
|
|||||||||||
"t9"
|
Error of fixed compressor discharge
sensor (Open/Short)
|
|
|
||||||||||
|
|
||||||||||||
"E1"
|
System down due to the communication
error after completion of tracking
|
||||||||||||
"E2"
|
Mismatching of the numbers of set
indoor units to actual indoor units
|
|
|||||||||||
"E3"
|
Indoor Unit float switch error
|
|
|
|
|||||||||
"E5"
|
Setting error of option switch in
indoor unit
|
|
|||||||||||
|
|
||||||||||||
"Ax"
|
Indoor Unit EVAP IN sensor breakaway
|
|
|
|
|||||||||
"bx"
|
Indoor Unit EVAP Out Sensor breakaway
|
|
|||||||||||
"Cx"
|
Electronic expansion valve open error
|
|
|
|
|||||||||
"dx"
|
Electronic expansion valve close
error
|
|
|||||||||||
"fx"
|
Simultaneous breakaway of indoor unit
EVAP IN and EVAP OUT sensor
|
|
|||||||||||
|
|
||||||||||||
"G2"
|
Total Leakage of Refrigerant in
outdoor unit/Loading Failure
|
|
|
||||||||||
"G3"
|
Breakaway of COND MID sensor in
outdoor unit
|
|
|||||||||||
"G6"
|
Breakaway of OIL temperature sensor
(Detected once or more times)
|
|
|||||||||||
"G7"
|
Breakaway of suction sensor
|
|
|||||||||||
"GC"
|
Breakaway of load compressor
discharge sensor
|
|
|
|
|||||||||
|
|
||||||||||||
"9x"
|
OPEN/SHORT error of room sensor in
indoor unit
|
|
|
|
|||||||||
"rx"
|
OPEN/SHORT of EVAP IN sensor in
indoor unit
|
|
|||||||||||
"yx"
|
OPEN/SHORT of EVAP OUT sensor in
indoor unit
|
|
|
|
|||||||||
"ux"
|
Error of fan setting
|
|
|||||||||||
|
|
||||||||||||
"tU"
|
Outdoor temperature being below -5
Deg. C when cooling mode
|
|
|||||||||||
"to"
|
Outdoor temperature being over 30
Deg. C when in heating mode
|
|
|||||||||||
|
|
||||||||||||
E101
|
Communication Error between the
indoor unit and the Panel
|
|
|
||||||||||
E121
|
|
||||||||||||
E122
|
|
|
|
||||||||||
E123
|
|
||||||||||||
E128
|
|
|
|
||||||||||
E129
|
|
||||||||||||
E130
|
Simultaneous breakaway of indoor unit
EVAP IN/OUT Sensor
|
|
|
||||||||||
E131
|
Auxiliary (electric) heater sensor 1
error
|
|
|||||||||||
E132
|
Auxiliary (electric) heater sensor 2
error
|
|
|
|
|||||||||
E133
|
Auxiliary (electric) heater sensor 3
error
|
|
|||||||||||
E134
|
Shutter sensor error
|
|
|
|
|
||||||||
E135
|
Perfect fan sensor Error
|
|
|||||||||||
E140
|
MCU temp. sensor open/short
|
|
|
|
|||||||||
E151
|
|
||||||||||||
E152
|
|
|
|
|
|||||||||
E153
|
|
||||||||||||
E154
|
|
|
|
|
|||||||||
E161
|
Mixed Operation error (operate heat
& cool mode at same time)
|
|
|||||||||||
E162
|
EPROM Error
|
|
|
|
|
||||||||
E163
|
Option setting error
|
|
|||||||||||
E165
|
Electric heater discharge temperature
protect error
|
|
|
|
|||||||||
E166
|
No fan error related to the electric
heater
|
|
|||||||||||
E167
|
S/W setup error in peripheral control
device using option
|
|
|
||||||||||
E180
|
|
||||||||||||
E181
|
|
||||||||||||
E182
|
The 2nd MCU SOL V/V error
|
|
|||||||||||
E190
|
There is no change of EVAP in
temperature during the piping check
|
|
|||||||||||
E191
|
There is no change of EVAP OUT
temperature during the piping check
|
|
|||||||||||
E192
|
EVAP IN temperature error during the
piping check
|
|
|
|
|||||||||
E193
|
EVAP OUT temperature error during the
piping check
|
|
|||||||||||
E201
|
|
|
|
||||||||||
E202
|
|
||||||||||||
E203
|
|
||||||||||||
E210
|
|
||||||||||||
E211
|
|
|
|||||||||||
E212
|
|
||||||||||||
E213
|
|
|
|||||||||||
E214
|
|
|
|||||||||||
E215
|
Indoor unit address in MCU error
|
|
|
|
|
||||||||
E216
|
DIP switch for indoor unit setting in
MCU set ON error
|
|
|||||||||||
E217
|
Dip switch for indoor unit setting in
MC set OFF error
|
|
|
||||||||||
E221
|
OUT-TEMP sensor OPEN/SHORT sensor
error
|
|
|||||||||||
E226
|
Out-Temp sensor breakaway
|
|
|
|
|
|
|||||||
E231
|
COND-OUT MAIN TEMP sensor error
OPEN/SHORT
|
|
|||||||||||
E236
|
COND-OUT MAIN TEMP sensor error
OPEN/SHORT
|
|
|
|
|||||||||
E241
|
COND-MID sensor breakaway of outdoor
unit
|
|
|||||||||||
E246
|
COND-OUT 1 breakaway
|
|
|
|
|
|
|||||||
E251
|
PWM DISCHARGE TEMP sensor error
OPEN/SHORT
|
|
|||||||||||
E256
|
Fixed capacity compressor 1 DCHRG
sensor error OPEN/SHORT
|
|
|||||||||||
E257
|
Fixed capacity compressor 2 DCHRG
sensor error OPEN/SHORT
|
|
|||||||||||
E258
|
Fixed capacity compressor 3 DCHRG
sensor error OPEN/SHORT
|
|
|||||||||||
E261
|
Digital discharge sensor breakaway
|
|
|||||||||||
E262
|
Fixed 1 discharge sensor breakaway
|
|
|
|
|
||||||||
E263
|
Fixed 2 discharge sensor breakaway
|
|
|||||||||||
E264
|
Fixed 3 discharge sensor breakaway
|
|
|
|
|
||||||||
E265
|
Sump-main breakaway error
|
|
|||||||||||
E266
|
Sump Sub 1 breakaway error
|
|
|
|
|
|
|||||||
E267
|
Sump Sub 2 breakaway error
|
|
|||||||||||
E268
|
Sump Sub 3 breakaway error
|
|
|
|
|
|
|||||||
E269
|
Suction breakaway error
|
|
|||||||||||
E271
|
SUMP TEMP DIGITAL sensor error
OPEN/SHORT
|
|
|
|
|||||||||
E276
|
SUMP TEMP FIXED 1 sensor error
OPEN/SHORT
|
|
|||||||||||
E277
|
SUMP TEMP FIXED 2 sensor error
OPEN/SHORT
|
|
|
|
|||||||||
E278
|
SUMP TEMP FIXED 3 sensor error
OPEN/SHORT
|
|
|||||||||||
E291
|
High pressure sensor error OPEN/SHORT
|
|
|
|
|
||||||||
E296
|
Low pressure sensor error OPEN/SHORT
|
|
|||||||||||
E301
|
High Pressure Sensor Breakaway
|
|
|
|
|
||||||||
E306
|
Low Pressure Sensor Breakaway
|
|
|||||||||||
E308
|
Suction Temp. Sensor ERROR
(OPEN/SHORT)
|
|
|
|
|||||||||
E312
|
Main Cooling sol. v/v open error
|
|
|||||||||||
E313
|
4-Way v/v operation error
|
|
|
|
|
|
|||||||
|
|
||||||||||||
E401
|
Outdoor unit freezing detection 1
|
|
|
|
|
||||||||
E402
|
Outdoor unit freezing detection 2
|
|
|||||||||||
E403
|
Outdoor unit freezing detection 3 -
freezing COMP DOWN
|
|
|
||||||||||
E404
|
Outdoor unit overload 1 protection control
error
|
|
|||||||||||
E405
|
Outdoor unit overload 2 protection
control error
|
|
|
|
|||||||||
E406
|
Outdoor unit overload 3 protection
control error
|
|
|||||||||||
E407
|
Compressor down by high pressire
sensor protection control 1
|
|
|||||||||||
E408
|
Compressor down by high pressire
sensor protection control 2
|
|
|||||||||||
E409
|
Compressor down by high pressire
sensor protection control 3
|
|
|||||||||||
E410
|
Compressor down by low pressure
sensor protection control 1
|
|
|||||||||||
E411
|
Compressor down by low pressure
sensor protection control 2
|
|
|||||||||||
E412
|
Compressor down by low pressure
sensor protection control 3
|
|
|||||||||||
E413
|
Outdoor unit SUMP DOWN 1 protection
control
|
|
|
|
|||||||||
E414
|
Outdoor unit SUMP DOWN 2 protection
control
|
|
|||||||||||
E415
|
Outdoor unit SUMP DOWN 3 protection
control
|
|
|
|
|||||||||
E416
|
Outdoor unit discharge temperature 1
protection control
|
|
|||||||||||
E417
|
Outdoor unit discharge temperature 2
protection control
|
|
|
||||||||||
E418
|
Outdoor unit discharge temperature 3
protection control
|
|
|||||||||||
E419
|
Outdoor unit EEV open 1 self
diagnosis error
|
|
|
|
|||||||||
E420
|
Outdoor unit EEV open 2 self
diagnosis error
|
|
|||||||||||
E421
|
Outdoor unit EEV open 3 self
diagnosis error
|
|
|
|
|||||||||
E422
|
Outdoor unit EEV close 1 self
diagnosis error
|
|
|||||||||||
E423
|
Outdoor unit EEV close 2 self
diagnosis error
|
|
|
|
|||||||||
E424
|
Outdoor unit EEV close 3 self diagnosis
error
|
|
|||||||||||
E425
|
Outdoor unit reverse phase detection
1 error
|
|
|
|
|||||||||
E426
|
Outdoor unit reverse phase detection
2 error
|
|
|||||||||||
E427
|
Outdoor unit reverse phase detection
3 error
|
|
|
|
|||||||||
E428
|
Outdoor unit compression rate 1 error
|
|
|||||||||||
E429
|
Outdoor unit compression rate 2 error
|
|
|
|
|
||||||||
E430
|
Outdoor unit compression rate 3 error
|
|
|||||||||||
E440
|
Forbid heating mode operation when
outdoor temperature over 30 Deg. C
|
||||||||||||
E441
|
Forbid cooling mode operation when
outdoor temperature below -5 Deg. C
|
||||||||||||
E442
|
Refrigerant charding error in the
heating mode
|
|
|
|
|||||||||
E452
|
Instant Power off (dissapear when
compresson run)
|
|
|||||||||||
|
|
||||||||||||
E551
|
Defrosting operation
|
|
|
|
|
|
|||||||
E552
|
Low Discharge Pressure
|
|
|||||||||||
E553
|
Eqability Operation
|
|
|
|
|
|
|
||||||
E554
|
Loading Failure Full leakage of
refrigerant of outdoor unit
|
|
|||||||||||
|
|
||||||||||||
E601
|
Communication error between wired
remote controller and indoor unit
|
|
|||||||||||
E602
|
Communication error between master
and slave wired remote controller
|
||||||||||||
E603
|
Communication error between 7 day
scheduler and wired remote controller
|
||||||||||||
|
|
||||||||||||
E701
|
Float S/W detection error
|
|
|
|
|
|
|||||||
E702
|
Indoor unit EEV closing error
|
|
|||||||||||
E703
|
Indoor unit EEV opening error
|
|
|
|
|
|
|||||||
E704
|
MCU Sol v/v failure
|
|
|||||||||||