Wednesday, 12 August 2015

Fujistu Air Conditioning Fault Codes For wireless indoor units AUY, ABY and AWY Models. Including Multi Systems (Not J Series or VRF)

Fujistu Air Conditioning Fault Codes For wireless indoor units AUY, ABY and AWY Models. Including Multi Systems (Not Series or VRF)





Red Light Operation
Green Light Timer
Yellow Light Swing

On


Normal
On
Slow Blink
Slow Blink
Test
Blinks
Blinks
Off
ID PCB Fail
Blinks
Blinks
Blinks
OD PCB Fail
Blinks
2 Pulses
Off
OD Power Connection Failure
Blinks
3 Pulses
Off
OD Unit Pipe Sensor Fail
Blinks
4 Pulses
Off
OD Unit Air Sensor Fail
Blinks
4 Pulses
Blinks
OD Unit Air Sensor Short
Blinks
5 Pulses
Off
OD Unit Discharge Sensor Fail
Blinks
5 Pulses
Blinks
OD Unit Discharge Sensor Short
Blinks
6 Pulses
Off
High Pressure
Blinks
7 Pulses
Off
High Discharge or Compressor Temp
Blinks
9 Pulses
Off
OD Unit Compressor Temp Sensor
Blinks
10 Pulses
Off
IPM Error
Blinks
11 Pulses
Off
CT Error
Blinks
12 Pulses
Off
AFM Filter Error
Blinks
13 Pulses
Off
Compressor Error
Blinks
14 Pulses
Off
OD Fan Motor Fail
2 Pulses
Blinks
Off
Air Sensor Open
2 Pulses
Blinks
Blinks
Air Sensor Closed
3 Pulses
Blinks
Off
Pipe Sensor Open
3 Pulses
Blinks
Blinks
Pipe Sensor Closed
4 Pulses
Blinks
Off
Drain Problem
5 Pulses
Blinks
Off
Communication Error
5 Pulses
Blinks
Blinks
OD PCB or Wiring Error
6 Pulses
Blinks
Off
Indoor Fan Failure
          




Contact Us With Your Spares Inquiry Below:


Call: +44(0)845 567 7080

E-mail: Info@orionair.co.uk 








No comments:

Post a Comment