Showing posts with label Fault Codes. Show all posts
Showing posts with label Fault Codes. Show all posts

Friday, 14 May 2021

Fujitsu air conditioning unit selector and fault codes 2021

 










Fujitsu Fault Codes:




Error Detail

Indoor LED Display Flashes

Wired RC

Operation

Timer

Economy

Serial communication error

1

1

Continuous

11

Wired RC communication error

1

2

Continuous

12

Network communication error

1

4

Continuous

14

Check run unfinished

1

5

Continuous

15

Transmission/Peripheral connect error

1

6

Continuous

16

Refrigeration circuit address setting error

2

1

Continuous

21

Indoor unit capacity error

2

2

Continuous

22

Combination error

2

3

Continuous

23

Connection unit number error

2

4

Continuous

24

Address setting error

2

6

Continuous

26

Master/Slave unit set-up error

2

7

Continuous

27

Connection unit number error in WRC circuit

2

9

Continuous

29

Power supply interruption error

3

1

Continuous

31

Indoor PCB EPPROM error

3

2

Continuous

32

Manual auto switch error

3

5

Continuous

35

Indoor unit WRC communication error

3

10

Continuous

3A

Inlet air temp sensor error

4

1

Continuous

41

Indoor Heat-Ex middle temp sensor error

4

2

Continuous

42

Indoor unit fan motor error

5

1

Continuous

51

Indoor EEV error

5

2

Continuous

52

Drain pump error

5

3

Continuous

53

Damper error

5

7

Continuous

57

Intake grille error

5

8

Continuous

58

Indoor unit error

5

15

Continuous

5U

Outdoor PCB/communication error

6

2

Continuous

62

Inverter error

6

3

Continuous

63

Active filter/PFC circuit error

6

4

Continuous

64

Trip terminal ‘L’ error

6

5

Continuous

65

Display PCB/communication error

6

10

Continuous

6A

OU Discharge temp sensor error

7

1

Continuous

71

Compressor temp sensor error

7

2

Continuous

72

OU Heat-Ex liquid temp sensor error

7

3

Continuous

73

OU Ambient temp sensor error

7

4

Continuous

74

OU Suction ref temp sensor error

7

5

Continuous

75

2/3 way valve temp sensor error

7

6

Continuous

76

OU Heat sink temp sensor error

7

7

Continuous

77

Sub-cool inlet/outlet temp sensor error

8

2

Continuous

82

OU Liquid pipe temp sensor error

8

3

Continuous

83

OU current sensor error

8

4

Continuous

84

HP/LP pressure sensor/switch error

8

6

Continuous

86

OU Current trip detection

9

4

Continuous

94

Compressor rotor location detection error

9

5

Continuous

95

OU fan motor error

9

7

Continuous

97

OU fan motor 2 error

9

8

Continuous

98

4-way valve error

9

9

Continuous

99

Coil (expansion valve) error

9

10

Continuous

9A

Outdoor unit error

9

15

Continuous

9U

OU Abnormal discharge temp error

10

1

Continuous

A1

Abnormal compressor temp error

10

3

Continuous

A3

High Pressure error

10

4

Continuous

A4

Low pressure error

10

5

Continuous

A5

VRF Branch box error

13

1

Continuous

J1

8-Way Multi branch box error

13

2

Continuous

J2

Accessories

PCB LED

PCB LED


WRC

VRF RB: Cable crossed OU/RB - IU/RB

on solid

on solid

-

-

VRF RB: Coms/Main PCB error

on solid

Continuous

-

-

WRC: Incompatible IU connected

-

-

-

C0:15

WRC: Indoor - WRC comms error

-

-

-

C0:12


Wednesday, 3 March 2021

SERVICE MANUAL AND FAULT CODES FOR SAMSUNG AIR CONDITIONING MODELS

 

SERVICE MANUAL AND FAULT CODES FOR SAMSUNG AIR CONDITIONING MODELS




https://drive.google.com/file/d/1npo8T59oFy39vWbR3_6fx8mmr3YM59Y5/view?usp=sharing





SAMSUNG MODELS:



WINDOW WALL:


AW09P1B, AW12P1B, AW18P1B, AW09P1HEA, AW12P1HEA, AW18P1HEA, AW24P1HEA AZ09PHB, AZ12PHA, AZ09PHHEA, AZ12PHHEA


5 WAY:

 SC09ZAB/7/8, SC12ZAB/7/8, SC18ZA(B)9, SC24TA(B)5 SH09ZAB/7/8, SH12ZAB/7/8, SH18ZA(B), SH24TA(B)5


DELUX:

SC09ZK8, SC12ZKG, SC18ZKO, SC24TK6, SC30OZC1/2 SC09ZS2, SC12ZS4, SC18ZS0A, SC24ZS6A, SH09ZK8, SH12ZKG, SH18ZKO, SH24TK6, SH30ZC1/2 SH09ZS2, SH12ZS4, SH18ZS0, SH24TS6


PREMIUM:

SH09ZP2/A, SH12ZP4/A, SH18ZP0(A), SH24TP6(A) 

CLASSIC:

SC09ZWH, SC12ZWH, SC18ZWJ, SC24ZW6, SH09ZWH, SH12ZWH, SH18ZWJ, SH24ZW6


PRESTIGE:

AS12HM3, AS18HM3, AS24HM3


FORTE :

AS09FAXFA, AS12FAXFA, AS18FAMID, AS24FAMID, AS30WB,AQ09FAXFA, AQ12FAXFA, AQ18FAMID, AQ24FAMID, AQ30WB AQ09NAMID, AQ12NAMID, AQ18NAMID, AQ24NAMID 

AQ09FCMID, AQ12FCMID, AQ18FEMID, AQ24FCMID


FORTE INVERTER:

AQV09NSAN, AQV12NSAN, AQV18NSAN, AQV24NSAN, AQV09FCN, AQV12FCN, AQV18FCN, AQV24FCN


MODERATO:

AQ09MWBNSER, AQ12MWBNSER, AQ18MWBNSER, AQ24WBNSER

AQ09MWBNAND, AQ12MWBNAND, AQ18MWBNAND, AQ24MWBNAND

AQ09MWBNMID, AQ12MWBNMID, AQ18MWBNMID, AQ24MWBNMID

AQ09MSBNSEU,AQ12MSBNSEU,  AQ18MSBNSEU,  AQ24MSBNSEU VIVACE                      -         

AQ09VB(W)AN, AQ12VB(W)AN, AQ18VB(W)AN, AQ24VB(W)AN


CASSETTE:

CH052EZMC, CH070EZMC, CH105EZMC, CH140EZMC

CH070EZM, CH105EZM1, CH140EZM1


DUCTED:

DH105GZM, DH140GZM, DH175GZM HH105EZM, HH140EZM, HH175EZM 

DH070EZM,


Thursday, 20 December 2018

Mitsubishi Heavy Industries Air Conditioning Fault Codes For PAC Multi Indoor and Outdoor systems ZHX-S, ZIX-S, ZJX-S,ZMX-S, ZSX-S

PAC SELF-DIAGNOSIS INFORMATION
Inverter PAC Outdoor

SRC

ZHX-S, ZIX-S, ZJX-S,ZMX-S, ZSX-S
Error Code
Indoor Unit Display
Outdoor
Control PCB,
Location of trouble
Description of trouble
Run Light
Green
Timer Light
Amber
Red LED

E35

Off

Flashing

2x

Installation, operation status

Higher outdoor heat exchanger temp
Outdoor heat exchanger temp sensor

Faulty outdoor heat exchanger temp sensor

Outdoor control PCB
Faulty outdoor control PCB (temperature sensor input circuit)

E36

Off

Flashing

5x

Installation, operation status

Higher discharge temperature
Discharge pipe temperature sensor

Faulty discharge pipe sensor

Outdoor control PCB
Faulty outdoor control PCB (temperature sensor input circuit)

E37

Off

Flashing

8x
Outdoor heat exchanger temp sensor
Faulty outdoor heat exchanger temp sensor, broken wire or poor connection

Outdoor control PCB
Faulty outdoor control PCB (temperature sensor input circuit)

E38

Off

Flashing

8x

Outdoor air temperature sensor
Faulty outdoor air temp sensor, broken wire or poor connection

Outdoor control PCB
Faulty outdoor control PCB (temperature sensor input circuit)

E39

Off

Flashing

8x
Discharge pipe temperature sensor
Faulty discharge pipe sensor, broken wire, poor connection

Outdoor control PCB
Faulty outdoor control PCB (temperature sensor input circuit)

E42

Off

Flashing

1x
Outdoor control PCB, compressor
Current cut (anomalous compressor ov er current)

Installation, operation status

Serv ice v alv e closing operation

E47

Off

Flashing

2x
Outdoor control PCB, power transistor

Anomalous inv erter ov er current

E48

Off

Flashing

Flashing

Outdoor fan motor

Faulty outdoor fan motor

Outdoor control PCB

Faulty outdoor control PCB

E51

Off

Flashing

1x
Power transistor, outdoor control PCB

Power transistor error

E57

Off

Flashing

2x

Operation status

Shortage of refrigerant

Installation status

Serv ice v alv e closed

E58

Off

Flashing

3x

Current safe stop
Ov erload operation, ov er charge, compressor locking

E59

Off

Flashing

2x

Compressor, outdoor control PCB

Anomalous compressor start up

E60

Off

Flashing

7x

Compressor

Anomalous compressor rotor lock




Technical Sales And Spares 


Tel: +44 (0)845 567 70 80

Fax: +44 (0)1234 780148



Skype: orionairsales
Orion Air Conditioning & Refrigeration Ltd
10 Grisedale Court,
Woburn Road Ind. Est.
Kempston,
Bedfordshire,
MK42 7EE,