RAC MULTISPLIT FAULT CODES - Current and Previous Models
|
||||||
Inverter Multi Indoor
|
SRK
|
ZJ-S,ZJ-S1,ZM-S,ZMX-S
|
ZJX-S, ZJX-S1
|
ZK-S
|
||
SRR
|
ZJ-S
|
|||||
SRF
|
ZJX-S, ZJX-S1,ZMX-S
|
|||||
FDT C
|
VD,VF, VF/1
|
|||||
FDUM
|
VF, VF/1
|
|||||
FDEN
|
VD, VF, VF/1
|
|||||
Inverter Multi
Outdoor
|
SCM
|
ZJ-S, ZJ-S1, ZM-S
|
||||
Indoor Unit Display
|
Outdoor Control PCB,
Red LED
|
Wired Remote Control
|
Description of Trouble
|
Possible Cause
|
||
Run Light
Green
|
Timer Light
Amber
|
|||||
-
|
-
|
-
|
E1
|
Error of wired remote Control
|
Broken wire, faulty indoor P.C.B., faulty controller.
|
|
-
|
-
|
1
|
E41
|
Power transistor ov erheat
|
Faulty power transistor or sensor.
|
|
-
|
-
|
2
|
E40
|
High pressure error
|
Faulty high pressure sensor, faulty control PCB, poor air circulation.
|
|
-
|
-
|
4
|
E45
|
Outdoor main or sub PCB communication error
|
Outdoor sub or main PCB faulty, poor connection of wires between outdoor PCBs
|
|
-
|
-
|
8
|
E54
|
High pressure sensor
|
Faulty high pressure sensor, faulty control PCB.
|
|
-
|
Flashing
|
-
|
E21
|
Limit switch error
|
Defectiv e limit switch, air inlet panel set, I/D control PCB
|
|
1x
|
ON
|
OFF
|
-
|
Indoor heat exchanger sensor (1) error
|
Broken heat exchanger sensor (1) wire, poor connection
|
|
2x
|
ON
|
OFF
|
-
|
Room temperature sensor
|
Broken room temperature sensor wire, poor connection
|
|
2x
|
2x
|
7x
|
E60
|
Rotor lock
|
Faulty compressor, open phase on compressor, faulty outdoor P.C.B.
|
|
3x
|
ON
|
OFF
|
-
|
Heat exchanger sensor 2 error
|
Broken heat exchanger sensor 3 wire, poor connection
|
|
4x
|
ON
|
OFF
|
E9
|
Drain error
|
Blocked drain, faulty float switch, faulty drain pump
|
|
5x
|
ON
|
2x
|
E47
|
Activ e filter v oltage error
|
Defectiv e Activ e Filter, incorrect power supply
|
|
6x
|
ON
|
OFF
|
E16
|
Indoor fan motor error
|
Faulty indoor fan motor, poor connection
|
|
7x
|
ON
|
2x
|
E57
|
Refrigerant cycle system protectiv e control
|
Closed serv ice v alv e, insufficient refrigerant
|
|
Flashing
|
1x
|
8x
|
E38
|
Outdoor air temperature sensor
|
Broken sensor wire, poor connection, faulty outdoor PCB
|
|
Flashing
|
2x
|
8x
|
E37
|
Outdoor heat exchanger sensor
|
Broken sensor wire, poor connection, faulty outdoor PCB
|
|
Flashing
|
4x
|
8x
|
E39
|
Discharge pipe sensor
|
Broken sensor wire, poor connection, faulty outdoor PCB
|
|
Flashing
|
5x
|
8x
|
E53
|
Outdoor suction sensor
|
Broken sensor wire, poor connection, faulty outdoor sub PCB
|
|
ON
|
1x
|
x1
|
E42
|
Current Cut
|
Compressor locking, open phase on compressor output, short circuit on power transistor, closed serv ice v alv e
|
|
ON
|
2x
|
2x
|
E59
|
Trouble of outdoor unit
|
discharge sensor wire or poor connection, compressor blockage
|
|
ON
|
3x
|
3x
|
E58
|
Current safe stop
|
Ov erload protection, ov er charged, compressor locking
|
|
ON
|
4x
|
1x
|
E51
|
Power transistor error
|
faulty inv erter PCB, faulty main PCB or faulty fan motor
|
|
ON
|
5x
|
5x
|
E36
|
Ov er heat of compressor
|
Low on gas, faulty discharge pipe senor, closed serv ice v alv e
|
|
ON
|
6x
|
6x
|
E5
|
Error of signal transmission
|
Defectiv e power supply, broken signal wire, faulty indoor/outdoor P.C.B.
|
|
ON
|
7x
|
Flashing
|
E48
|
Outdoor fan motor or main PCB
|
Faulty condenser fan motor or faulty main PCB
|
|
ON
|
Flashing
|
2x
|
E35
|
Cooling High Pressure Protection
|
Ov erload protection, ov er charged, broken outdoor heat exchanger sensor wire, closed serv ice v alv e
|
Technical Sales And Spares
Tel: +44 (0)845 567
70 80
Fax: +44 (0)1234
780148
e-mail: info@orionair.co.uk
Skype: orionairsales
Orion Air
Conditioning & Refrigeration Ltd
10 Grisedale Court,
Woburn Road Ind.
Est.
Kempston,
Bedfordshire,
MK42 7EE,
United Kingdom
No comments:
Post a Comment