Mitsubishi Heavy Industries Air Conditioning Fault Codes For RAC Multi-Split Indoor and Outdoor systems

RAC MULTISPLIT FAULT CODES - Current and Previous Models

Inverter Multi Indoor
SRK
ZJ-S,ZJ-S1,ZM-S,ZMX-S
ZJX-S, ZJX-S1
ZK-S
SRR
ZJ-S
SRF
ZJX-S, ZJX-S1,ZMX-S
FDT C
VD,VF, VF/1
FDUM
VF, VF/1
FDEN
VD, VF, VF/1
Inverter Multi
Outdoor

SCM
ZJ-S, ZJ-S1, ZM-S
Indoor Unit Display
Outdoor Control PCB,
Red LED
Wired Remote Control
Description of Trouble
Possible Cause

Run Light

Green
Timer Light
Amber

-

-

-

E1

Error of wired remote Control

Broken wire, faulty indoor P.C.B., faulty controller.

-

-

1

E41

Power transistor ov erheat

Faulty power transistor or sensor.

-

-

2

E40

High pressure error
Faulty high pressure sensor, faulty control PCB, poor air circulation.

-

-

4

E45
Outdoor main or sub PCB communication error
Outdoor sub or main PCB faulty, poor connection of wires between outdoor PCBs

-

-

8

E54

High pressure sensor

Faulty high pressure sensor, faulty control PCB.

-

Flashing

-

E21

Limit switch error

Defectiv e limit switch, air inlet panel set, I/D control PCB

1x

ON

OFF

-
Indoor heat exchanger sensor (1) error

Broken heat exchanger sensor (1) wire, poor connection

2x

ON

OFF

-

Room temperature sensor

Broken room temperature sensor wire, poor connection

2x

2x

7x

E60

Rotor lock
Faulty compressor, open phase on compressor, faulty outdoor P.C.B.

3x

ON

OFF

-

Heat exchanger sensor 2 error

Broken heat exchanger sensor 3 wire, poor connection

4x

ON

OFF

E9

Drain error

Blocked drain, faulty float switch, faulty drain pump

5x

ON

2x

E47

Activ e filter v oltage error

Defectiv e Activ e Filter, incorrect power supply

6x

ON

OFF

E16

Indoor fan motor error

Faulty indoor fan motor, poor connection

7x

ON

2x

E57
Refrigerant cycle system protectiv e control

Closed serv ice v alv e, insufficient refrigerant

Flashing

1x

8x

E38

Outdoor air temperature sensor

Broken sensor wire, poor connection, faulty outdoor PCB

Flashing

2x

8x

E37

Outdoor heat exchanger sensor

Broken sensor wire, poor connection, faulty outdoor PCB

Flashing

4x

8x

E39

Discharge pipe sensor

Broken sensor wire, poor connection, faulty outdoor PCB

Flashing

5x

8x

E53

Outdoor suction sensor
Broken sensor wire, poor connection, faulty outdoor sub PCB

ON

1x

x1

E42

Current Cut
Compressor locking, open phase on compressor output, short circuit on power transistor, closed serv ice v alv e

ON

2x

2x

E59

Trouble of outdoor unit
discharge sensor wire or poor connection, compressor blockage

ON

3x

3x

E58

Current safe stop

Ov erload protection, ov er charged, compressor locking

ON

4x

1x

E51

Power transistor error

faulty inv erter PCB, faulty main PCB or faulty fan motor

ON

5x

5x

E36

Ov er heat of compressor
Low on gas, faulty discharge pipe senor, closed serv ice v alv e

ON

6x

6x

E5

Error of signal transmission
Defectiv e power supply, broken signal wire, faulty indoor/outdoor P.C.B.

ON

7x

Flashing

E48

Outdoor fan motor or main PCB

Faulty condenser fan motor or faulty main PCB

ON

Flashing

2x

E35

Cooling High Pressure Protection
Ov erload protection, ov er charged, broken outdoor heat exchanger sensor wire, closed serv ice v alv e


  