PAC SELF-DIAGNOSIS INFORMATION
|
||||||
Inverter PAC Outdoor
|
SRC
|
ZHX-S, ZIX-S, ZJX-S,ZMX-S, ZSX-S
|
||||
Error Code
|
Indoor Unit Display
|
Outdoor
Control PCB,
|
Location of trouble
|
Description of trouble
|
||
Run Light
Green
|
Timer Light
Amber
|
|||||
Red LED
|
||||||
E35
|
Off
|
Flashing
|
2x
|
Installation, operation status
|
Higher outdoor heat exchanger temp
|
|
Outdoor heat exchanger temp sensor
|
Faulty outdoor heat exchanger temp sensor
|
|||||
Outdoor control PCB
|
Faulty outdoor control PCB (temperature sensor input circuit)
|
|||||
E36
|
Off
|
Flashing
|
5x
|
Installation, operation status
|
Higher discharge temperature
|
|
Discharge pipe temperature sensor
|
Faulty discharge pipe sensor
|
|||||
Outdoor control PCB
|
Faulty outdoor control PCB (temperature sensor input circuit)
|
|||||
E37
|
Off
|
Flashing
|
8x
|
Outdoor heat exchanger temp sensor
|
Faulty outdoor heat exchanger temp sensor, broken wire or poor connection
|
|
Outdoor control PCB
|
Faulty outdoor control PCB (temperature sensor input circuit)
|
|||||
E38
|
Off
|
Flashing
|
8x
|
Outdoor air temperature sensor
|
Faulty outdoor air temp sensor, broken wire or poor connection
|
|
Outdoor control PCB
|
Faulty outdoor control PCB (temperature sensor input circuit)
|
|||||
E39
|
Off
|
Flashing
|
8x
|
Discharge pipe temperature sensor
|
Faulty discharge pipe sensor, broken wire, poor connection
|
|
Outdoor control PCB
|
Faulty outdoor control PCB (temperature sensor input circuit)
|
|||||
E42
|
Off
|
Flashing
|
1x
|
Outdoor control PCB, compressor
|
Current cut (anomalous compressor ov er current)
|
|
Installation, operation status
|
Serv ice v alv e closing operation
|
|||||
E47
|
Off
|
Flashing
|
2x
|
Outdoor control PCB, power transistor
|
Anomalous inv erter ov er current
|
|
E48
|
Off
|
Flashing
|
Flashing
|
Outdoor fan motor
|
Faulty outdoor fan motor
|
|
Outdoor control PCB
|
Faulty outdoor control PCB
|
|||||
E51
|
Off
|
Flashing
|
1x
|
Power transistor, outdoor control PCB
|
Power
transistor error
|
|
E57
|
Off
|
Flashing
|
2x
|
Operation status
|
Shortage of refrigerant
|
|
Installation status
|
Serv ice v alv e closed
|
|||||
E58
|
Off
|
Flashing
|
3x
|
Current safe stop
|
Ov erload operation, ov er charge, compressor locking
|
|
E59
|
Off
|
Flashing
|
2x
|
Compressor, outdoor control PCB
|
Anomalous compressor start up
|
|
E60
|
Off
|
Flashing
|
7x
|
Compressor
|
Anomalous compressor rotor lock
|
Technical Sales And Spares
Tel: +44 (0)845 567
70 80
Fax: +44 (0)1234
780148
e-mail: info@orionair.co.uk
Skype: orionairsales
Orion Air
Conditioning & Refrigeration Ltd
10 Grisedale Court,
Woburn Road Ind.
Est.
Kempston,
Bedfordshire,
MK42 7EE,
United Kingdom
No comments:
Post a Comment