PAC SELF-DIAGNOSIS INFORMATION
|
|||||||
Inverter PAC
Outdoor
|
FDCVA
|
HEN, HENR, HENAR
|
|||||
FDC
|
VN, VNP, VS, VSA, VNX,VSX
|
||||||
Error Code
|
Indoor PCB LEDs
|
Outdoor unit LEDs
|
Description of Fault
|
Possible Cause
|
|||
RED
|
GREEN (1)
|
RED
|
GREEN (1)
|
INV LED
|
|||
E33
|
Off
|
Flashing
|
1x
|
Flashing
|
-
|
Power supply
|
Anomalous current on inv erter primary side
|
E34
|
Off
|
Flashing
|
1x
|
Flashing
|
Flashing
|
Power supply
|
Phase open
circuit,
faulty outdoor control PCB (3 Phase model)
|
E35
|
Off
|
Flashing
|
1x
|
Flashing
|
Flashing
|
Outdoor heat exchanger thermistor
|
Ov erheat of condenser, faulty thermistor, faulty outdoor PCB
|
E36
|
Off
|
Flashing
|
1x
|
Flashing
|
Flashing
|
Discharge pipe thermistor
|
High discharge temp, faulty sensor,
faulty outdoor control PCB
|
E37
|
Off
|
Flashing
|
1x
|
Flashing
|
Flashing
|
Outdoor heat exchanger thermistor
|
Poor connection, broken
wire, faulty thermistor, faulty PCB
|
E38
|
Off
|
Flashing
|
1x
|
Flashing
|
Flashing
|
Outdoor ambient air sensor
|
Poor connection, broken
wire, faulty thermistor, faulty PCB
|
E39
|
Off
|
Flashing
|
1x
|
Flashing
|
Flashing
|
Discharge pipe thermistor
|
Poor connection, broken
wire, faulty thermistor, faulty PCB
|
E40
|
Off
|
Flashing
|
1x
|
Flashing
|
Flashing
|
High Pressure Error
|
Activ ation
of
HP switch (63H1), closed serv ice v alv e, faulty PCB (63H1 Circuit)
|
E41
|
Off
|
Flashing
|
1x
|
Flashing
|
2 or 6x
|
Power Transistor ov erheat
|
S hort circuit of air flow, faulty Inv erter PCB
|
E42
|
Off
|
Flashing
|
1x
|
Flashing
|
1 or 5x
|
Current Cut
|
Closed serv ice v alv e, faulty outdoor control PCB
|
E45
|
Off
|
Flashing
|
1x
|
Flashing
|
Flashing
|
Communication
Error
- Inv erter to Control PCB
|
Poor Connection, faulty control or inv erter PCBs
|
E47
|
Off
|
Flashing
|
1x
|
Flashing
|
7x
|
Control PCB, Power transistor
|
Anomalous inv erter ov er v oltage
|
E48
|
Off
|
Flashing
|
1x
|
Flashing
|
Flashing
|
Condenser fan
motor
|
Faulty fan motor or outdoor PCB
|
E49
|
Off
|
Flashing
|
1x
|
Flashing
|
Flashing
|
Low Pressure Error
|
Closed serv ice v alv e, short of gas, faulty LP sensor, faulty outdoor control PCB
|
E51
|
Off
|
Flashing
|
1x
|
Flashing
|
2 or 6x
|
Inv erter Error
|
Faulty Inv erter PCB
|
E53
|
Off
|
Flashing
|
1x
|
Flashing
|
Flashing
|
S uction pipe thermistor
|
Poor connection, broken
wire, faulty thermistor, faulty PCB
|
E54
|
Off
|
Flashing
|
1x
|
Flashing
|
Flashing
|
Low Pressure S ensor Error
|
Closed serv ice v alv e, short of gas, faulty LP sensor, faulty outdoor control PCB
|
E55
|
Off
|
Flashing
|
1x
|
Flashing
|
Flashing
|
Under-dome temp thermistor
|
Poor connection, broken
wire, faulty thermistor, faulty PCB
|
E57
|
Off
|
Flashing
|
1x
|
Flashing
|
Flashing
|
Low Pressure Error
|
Insufficient refrigerant
|
E59
|
Off
|
Flashing
|
5x
|
Flashing
|
Off or 4x
|
Compressor start up error
|
Faulty power supply, faulty inv erter circuit.
|
E60
|
Off
|
Flashing
|
1x
|
Flashing
|
-
|
Compressor
|
Faulty compressor, faulty
inv erter circuit.
|
E75
|
Off
|
Flashing
|
Off
|
Flashing
|
-
|
Central Controller communication error
|
Poor connection, broken
wire, faulty controller
|
Technical Sales And Spares
Tel: +44 (0)845 567
70 80
Fax: +44 (0)1234
780148
e-mail: info@orionair.co.uk
Skype: orionairsales
Orion Air
Conditioning & Refrigeration Ltd
10 Grisedale Court,
Woburn Road Ind.
Est.
Kempston,
Bedfordshire,
MK42 7EE,
United Kingdom
No comments:
Post a Comment