PAC SELF-DIAGNOSIS INFORMATION
|
||||||
Inverter PAC
Indoor Units
|
FDT
|
V, VD, VF, VF/1, VG
|
||||
FDTC
|
V, VD, VF, VF/1,
|
|||||
FDU
|
VF, VF/1, VG
|
|||||
FDUM
|
1, 1R, V, VD, VF, VF/1
|
|||||
FDE
|
VG
|
|||||
FDEN
|
V, VD, VF, VF/1
|
|||||
FDF
|
VD
|
|||||
Error Code
|
Indoor PCB LEDs
|
Outdoor unit LEDs
|
Description of Fault
|
Possible Cause
|
||
RED
|
GREEN (1)
|
RED
|
GREEN (1)
|
|||
No Error Code
|
Off
|
Flashing
|
Off
|
Flashing
|
-
|
Normal Operation
|
Off
|
Off
|
2x
|
Off
|
Indoor unit power supply
|
Power OFF, broken wire, blown fuse, broken transformer wire
|
|
3x
|
Flashing
|
Off
|
Flashing
|
Remote controller wires
|
Poor or wrong connection, broken wire
|
|
Remote controller
|
Faulty Remote controller
|
|||||
"W AIT" or "INSPECT I/U"
|
Off
|
Flashing
|
2x
|
Flashing
|
Communication error (indoor-outdoor)
|
Faulty interconnect wiring, faulty PCB
|
Remote Controller
|
Improper setting of master and slav e by Remote Controller
|
|||||
E1
|
Off
|
Flashing
|
Off
|
Flashing
|
Communication error (indoor-remote control)
|
Poor or wrong connection, broken wire, intrusion
of noise, faulty indoor PCB or
|
E5
|
2x
|
Flashing
|
2x
|
Flashing
|
Indoor
- Outdoor communication fault
|
Poor connection, incorrect wiring, indoor or outdoor PCB
|
2x
|
Flashing
|
Off
|
Flashing
|
Electrical Noise
|
CPU Runaway on Outdoor control PCB
|
|
Outdoor Control PCB
|
Faulty Outdoor Control PCB (Communication Circuit)
|
|||||
2x
|
Flashing
|
Off
|
Off
|
Outdoor Control PCB
|
Faulty Outdoor Control PCB or Power supply
|
|
E6
|
1x
|
Flashing
|
Off
|
Flashing
|
Indoor heat exchanger temp sensor
|
Faulty sensor, poor connection, faulty indoor PCB
|
E7
|
1x
|
Flashing
|
Off
|
Flashing
|
Indoor return air temp sensor
|
Faulty sensor, poor connection, faulty indoor PCB
|
E8
|
1x
|
Flashing
|
Off
|
Flashing
|
Indoor heat exchanger temp sensor
|
Heating ov erload, faulty sensor, faulty indoor PCB
|
E9
|
1x
|
Flashing
|
Off
|
Flashing
|
Float switch activ ated
|
Blocked drain, faulty pump, faulty indoor PCB, faulty float switch
|
E10
|
Off
|
Flashing
|
Off
|
Flashing
|
No. of indoor units connected
|
Too many units connected to 1 controller (MAX 16)
|
E14
|
3x
|
Flashing
|
Off
|
Flashing
|
Remote controller Fault
|
No master assigned to slav es, incorrect wiring, broken wire between master &
|
E16
|
1x
|
Flashing
|
Off
|
Flashing
|
Indoor fan motor
|
Faulty Indoor fan motor, poor connection, faulty indoor PCB
|
E18
|
1x
|
Flashing
|
Off
|
Flashing
|
Address S etting Error
|
Address setting error of master and slav e indoor units
|
E19
|
1x
|
Flashing
|
Off
|
Flashing
|
Mode Setting
|
Incorrect mode setting
|
E20
|
1x
|
Flashing
|
Off
|
Flashing
|
Indoor fan motor
|
Fan motor speed fault or faulty indoor Power PCB
|
E21
|
1x
|
Flashing
|
Off
|
Flashing
|
Panel Limit S witch error
|
Defectiv e limit switch, air inlet panel set, I/D control PCB
|
E28
|
Off
|
Flashing
|
Off
|
Flashing
|
Remote Controller temp sensor
|
Faulty Remote controller temp sensor
|
Technical Sales And Spares
Tel: +44 (0)845 567
70 80
Fax: +44 (0)1234
780148
e-mail: info@orionair.co.uk
Skype: orionairsales
Orion Air
Conditioning & Refrigeration Ltd
10 Grisedale Court,
Woburn Road Ind.
Est.
Kempston,
Bedfordshire,
MK42 7EE,
United Kingdom
No comments:
Post a Comment